35kV Cable
- - Conductor:High-purity annealed copper or aluminum conductor, available in various cross-sections (50mm² to 800mm²).
- - Insulation:XLPE (Cross-linked Polyethylene) or HEPR (Hard Ethylene Propylene Rubber) insulation, offering excellent thermal stability, high dielectric strength, and long-term aging resistance for 35kV high-voltage systems.
Product Introduction
35kV Cable – Key Specifications & Construction
– Conductor:High-purity annealed copper or aluminum conductor, available in various cross-sections (50mm² to 800mm²).
– Insulation:XLPE (Cross-linked Polyethylene) or HEPR (Hard Ethylene Propylene Rubber) insulation, offering excellent thermal stability, high dielectric strength, and long-term aging resistance for 35kV high-voltage systems.
– Screen/Sheath:Triple-layer semi-conductive and metallic copper screen to precisely control electric fields and eliminate partial discharges; outer sheath (PVC, PE, or halogen-free LSZH compound) provides robust protection against oils, chemicals, UV radiation, and mechanical damage.
– Armoring:Optional galvanized steel wire armor (SWA) or steel tape armor (STA) for enhanced mechanical protection against crushing, impact, rodent damage, and tensile stress in heavy-duty installation scenarios.
– Voltage Rating:35kV (26/35kV, 21/35kV, 18/30kV(36kV))
– Standards Compliance:IEC 60502-2, IEC 60228, IEC/EN 60332-1-2, GB/T 12706, GB/T 11017
Technical Specifications of RS 35kV Cable
| Item | Parameter | Details |
|---|---|---|
| Conductor | Material | High-purity annealed Copper (Cu) / Aluminum (Al) |
| Standard | IEC 60228 (Class 2/5) | |
| Cross-section | 50 mm² ~ 800 mm² (Customizable) | |
| Insulation | Material | XLPE (Cross-linked PE) / HEPR (Hard EPR) |
| Thickness | ≥ 10.0 mm (per IEC 60502-2 for 26/35kV) | |
| Temp. Rating | 90°C (continuous); 130°C (short-term) | |
| Dielectric Strength | ≥ 30 kV/mm (DC) | ≥ 20 kV/mm (AC) | |
| Volume Resistivity | ≥ 1×10¹⁴ Ω·m (20°C) | |
| Screen | Inner Screen | Semi-conductive XLPE compound (thickness ≥ 1.5 mm) |
| Metallic Screen | Copper tape (≥ 0.20 mm) / Copper strands (Mandatory) | |
| Outer Screen | Semi-conductive PE sheath (thickness ≥ 1.5 mm) | |
| Grounding Resistance | ≤ 0.3 Ω/km (20°C) | |
| Armoring | Type | SWA (Steel Wire) / STA (Steel Tape) (Optional) |
| Outer Sheath | Material | PVC / PE / LSZH (Halogen-free) |
| Performance | Bending Radius | ≥ 20D (Armored) / ≥ 15D (Unarmored) |
| Standards | Compliance | IEC 60502-2, GB/T 12706, GB/T 11017, CE, ISO 9001 |